EVAX25/EVAX50/EVAX100
TERMINAL DESIGNATIONS
TB1:
14
14
TER1&2
TER3&4
TER5&6
-PowerInput24-32V AC/DC(NOTE , )
-FACP SignalCircuitInput-10mA max.(AlarmPolarityshown)(NOTE
, )
-25/70VRMSSpeakerLoopStyle Y/Z(Class “A/Bstart) (NOTE ,2
TB3:
14
135
TER1&2
TER3&4
TER5&6
TER7
(NOTE , )
FACP Signal/Supervisory
CircuitEOLR
MatchingEOLRforspeaker
supervisorycircuit
(NOTE , , )
Generalpurposeoutput(pulls
tocircuitnegonfault
condition
32V-0.2A max).NotforFire
ProtectiveSignalinguse.
OptionalFACP Supervisory
Circuit(Seeinstallation
instructionspage5diagram2
fordetails(32V-0.4A max.)).
Factorysetfornone-J1
(installed)
NOTES:
-Intendedforconnectionto
ListedClass2/Class3(Power
Limited)sourcesonly.
-PowerLimited
-Non-Supervised
-Supervised
- Terminatingequipmentmust
beinstalledinsameroomas
1
2
3
4
5
1=OFF8sec.initialdelay
2=ON
3=OFF
4=ON8sec.repeatdelay
5=OFF
6=ONMessageOn
7=OFF3Repeats
8=ON
SN1
FACTORY DEFAULTSWITCH/JUMPERSETTINGS:
1-2=SHORT
J1 A/B
1+2SHORT =GroundFaultEnable
J5
25VRMS2-3=SHORT
70VRMS1-2=SHORT
J2
Tochangeoutputvoltage
moveshortingblock.
SN2
1=OFF TemporalWhoopSignal
2=OFF
3=OFF
4=FaultCodeLock
5=XDonotuse
6= ACFaultDelay
7=ONBatteryconnected
8=ONMicconnected
(defaultup(off))
(defaultup(off))
1 8
ON
OFF
SwitchNetworkDetail
TB2:
13
135
135
135
13
13
235
23
23
5
-CircuitNeg
(NOTE , )
Aux AudioInput
(0.5Vnominal)
(1VRMS-1mA max.)
(NOTE , , )
PreAmpIn/Out
(600Ohm0dBm)
(NOTE , , )
Master-Programmable
+24VDC Active
Slave-+24VDCInput
(NOTE , , )
Signal Active
Master-Out/Slave-In
(NOTE , )
Aux AudioEnable
(+24V)(32V-5mA max.)
(NOTE , )
AuxSignal Activate
(+24V)(32V-5mA max.)
(NOTE , , )
AlarmVoltage+24V
whenunitisinalarm
condition(0.1A)
(NOTE , )
IntV+(+24V)
disconnectedinalarm
condition(0.1A)
(NOTE , )
V+(+24V0.1A)
(NOTE )
MicPTT (+24V0.1A)
TER1
TER2
TER3
TER4
TER5
TER6
TER7
TER8
TER9
TER10
TER11
1
2
TB1
1 2 3
4
5 6 7 8
TB3
1
2
3
4
5
6
7
8
MSG
GAIN
MIC
GAIN
FAULT
NORMAL
ALARM
YEL
YEL
GROUND
FAULT
GRN
RED
TB2
1
2
3
4
5
6
7
8
9
10
11
P2
U6
S1
SN2 SN1
1 2 3
J2
J5
J1
1
2
70V25V
1
2
3
4
Fieldwiringconnections:
#6-32wireclampscrew14-18 AWG
#8-32wireclampscrew12-18 AWG
Horizontalwireentryterminal18-26 AWG
Wiregaugedeterminedbycircuitload
HARRINGTON
FIREALARM
SIGNALINC.
ISO9001Certified
25194th AvenueMoline,IL 61265
(309)762-0731FAX(309)762-8215
www.harringtonsignal.com
P/N1-5001REV.G
Page2of8